AN ORDINANCE OF THE CITY OF FORT WALTON BEACH RELATING TO
FIRE SPRINKLER SYSTEMS, AMENDING SECTION 1420.01,
INSTALLATION REQUIRED IN CERTAIN BUILDINGS; STANDARDS; PUMPS;
OBSTRUCTIONS; OF THE CODIFIED ORDINANCES OF THE CITY; AND
PROVIDING FOR AN EFFECTIVE DATE.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF FORT
WALTON BEACH, FLORIDA:
SECTION 1. SECTION 1420.01, INSTALLATION REQUIRED IN CERTAIN
BUILDINGS; STANDARDS; PUMPS; OBSTRUCTIONS; OF THE CODIFIED ORDINANCES OF THE
CITY AMENDED. Section 1420.01, Installation Required in Certain Buildings;
Standards; Pumps; Obstructions; of the Codified Ordinances of the City is
amended to read:
1420.01 INSTALLA TE ON--REQU-ERED —-EN--CERTAIN--BUTEDINGS ; —- STANDARDS
PUMPS+-OBSPRUETIONS: DEFINITIONS.
For the purposes of this Section, the following definitions shall
apply:
(a) "Gross Floor Area" shall mean the inside perimeter of the
exterior walls with no deduction for corridors, stairs, closets,
thickness of walls, columns or other features exclusive of areas open
and unobstructed to the sky.
(b) "Height" shall mean the vertical distance from the lowest
finished floor to the highest point of the roof, Church steeples,
cupolas, equipment enclosures, and chimneys are exempt from this
definition.
1420.02 INSTALLATION REQUIRED IN CERTAIN BUILDINGS; STANDARDS; PUMPS;
OBSTRUCTIONS.
(a) All buildings constructed in the city that are three stories
or thirty feet in height or higher or exceed 12,000 gross floor area
regardless of interior separations shall be protected by automatic
sprinkler systems throughout the entire building.;-~-with--the
exception-of-church-sanectuariess Existing buildings at the time of
the adoption of this ordinance shall be required to be sprinklered if
an addition, alteration, or rehabilitation occurs to the building
equal to or greater than fifty (50) percent of the original building
gross floor area and such floor area increases shall be cumulative.
(b) All such sprinkler systems shall be installed strictly
in accordance with the standards set forth in the National Fire Codes,
as adopted in Section 1610.01 of the Fire Prevention Code; the
Standard Building Code as adopted in Section 1420.01; and N.F.P.A. No.
13, No. 13D, and No. 13R as amended, except that such system shall be
installed throughout the building as set forth in subsection (a)
hereof.
(c) Automatic sprinkler systems shall be provided with separate
pumps when necessary. The pump shall be physically located in a
separate building apart from the sprinklered structure or have a
four two-hour fire-wati separation to protect the pump from a
fire in the main building. A door shall be installed to the pump room
to gain entrance from the outside.
LITHO BY VITRO PRESS
(d) There shall be no obstruction within ten feet of the fire
department connection to the automatic sprinkler system. All fire
department connections shall be provided with a reflective sign
approved by the fire department for ease of location.
SECTION 2. EFFECTIVE DATE. This ordinance shall take effect
immediately upon approval by council and signature of the Mayor.