operation of remote site
dial-up communications,
Verify sefup of users, passwords and
privilege levels to agreed upon “as builts”.
Correct records and/or differences as noted.
Verify setup and operation of maintenance
time reminder applications.
Verify operation of print screen
documentation capability.
Verify setup and operation of LAN device
communications.
‘Synchronize network clock operations.
Verify setup and operation of status log
reports.
Verify setup and operation of point summary
reports.
Service Procedure Function Benefit Recommended
Frequency
Device Database Backup Provide backup of system databases to hard disk Ensures on-site PC files are maintained at Annually
system. operating standard,
Provide backup to Hoppy disketfe of archived trend Ensures accurnulated data may be recovered for
data files for long-term storage. lates analysis. =~
Provide hard disk backup of data files to off-site Protects total systern from catastrophic loss or
storage location. mMaticious damage by providing off-site archived
Provide hard disk backup of data files to on-site storage,
storage location, Provides an on-site backup of system for fast
Perform routine disk file maintenance. recovery in event of catastrophic failure.
Ensures that disk Is organized and clear of data
previously saved to backup disk.
Systems Specialists, inc.
The BEST in ENVIRONMENTAL CONTROLS
Page 9 of 11
Systems Specialists, Inc.
Authorized Representative
Barber-Colman, Siebe & invensys Building Systems, TAC
114 East Wright Street
’ Pensacola, FL 32507
Phone: (850) 472-2147
MAINTENANCE SERVICES Fax: (850) 472-2146
NETWORK 8000 GCM, MICROZONE, PEM
Service Procedure Functlon Benefit Recommended
Frequency
Verify Controller Database and Compareiverify each LCM/GCM device Database verification ensures DDC Annually
Modifications database matches agreed upon Owner "as system cperates and performs as
built’ prints and records, designed to meet goals for energy
eduction and comfort performance.
identify alf additions, modifications, and
changes to software sequences, setpolnts, Eliminates “creeping decay” of
schedules and limits. operational performance saused by non-
removal of “temporary” bypasses, ets.
Provide assessment report to Qwner of
impact of all noted changes. Provides Owner-with recommended
courses of action to Improve performance
Update “as built’ records and database ‘over time,
storage files with Owner approved changes.
Verlfy Operation of Remote initiate communications with DDG control Provides continuous check of sarvica Semi Annually
Telecommunication Datalink to network . Tesponse mechanism.
Remote Site
Verify alarm dial-out capabilities to service Detects failure of third party datalink.
contractor. -
Remote Service Provide routine database backup service of Reduces downtime by having a current Annually
. all operating controller databases. database available for replacement.
‘On-Site Service
In the event of catastrophic failure, download | Provides an off-site record archiving
database to replacement device. depot as protection against catastrophic
failure, theft and malicious damage to
Update device database to current operating databases,
standards,
Gheck Device Battery ‘Verify proper operation of battery backup. Ensure historical data integrity is Semi Annually
maintained for diagnostic purposes.
Visual Inspection Ensure device is not physically damaged. £nsure there are not impending failures Semi Annually
which can adversely affect system
Report all damaged components, operation and inteatity.
Systems Specialists, Inc.
The BEST in ENVIRONMENTAL CONTROLS
Page 10 of 11
Systems Specialists, Inc.
Authorized Representative
Barber-Colman, Siebe & Invensys Building Systems, TAC
MAINTENANCE SERVICES
NETWORK 8000 MIGROZONE & PEM
114 East Wright Street
Pensacola, FL 32501
Phone: (850) 472-2147
Fax: (850) 472-2146
Verifies proper input to after-hours billing
programs.
Maximizes energy efficiency of systems by
employing scheduled control operations.
Service Procedure Function Benefit Recommended
_ Frequency
Check Sequence of Mechanicat Verify that controlled equipment properly Ensures that system operates as designed ‘Semi annually
Cperation cycles from full haat to full cool. to provide proper occupant comfort. Heating in Fall
Cooling In Spring
Check Room Sensor Accuracy Verify operational accuracy of room sensor Ensures comfort of occupants Is provided Annually
within 40.5°F.
Check Zone Occupancy Override Verify that conirollad systems switch from Ensures after-hours comfart of eccupanis. Annually
Operation unoccupied to occupied modes,
Sysiems Specialisis, inc.
The BEST in ENVIRONMENTAL CONTROLS
Page 14 of 14