and negative flow for a 4250 Area Velocity Flow Meter.
b. The software shall include diagnostics to display the signal strength and spectrum
strength from an Isco Area Velocity Flow Meter, and the signal strength from an Isco
Ultrasonic Flow Meter. The diagnostics shall also display status messages from a 4200
Series Flow Meter for power failed, paper out, pdnterjammed, and printer power.
4. Device Setup
a. The software shall set the site name, instrument date and time, and password for each
flow meter, and zero the totalizer in the flow meter. The software shall set the variable
blanking distance for an Isco Ultrasonic Flow Meter. The software shall set the zero level
offset and the set flow rate to zero if no velocity data setting for an Isco Area Velocity
Flow Meter, and the minimum depth for velocity measurement for an Ism Area Velocity
Flow Meter with a Standard Area Velocity Sensor.
b. The software shall display and save to a file the program, two summary reports, and
history report from a 4200 Series Flow Meter.
5. Data Storage
a. The software shall divide the memory in a 4100 Series Flow Logger into up to 6 memory
partitions, and shall divide the memory in a 4200 Series Flow Meter into up to 12
memory partitions. Each partition shall store level, velocity, flow rate, rainfall, pH,
dissolved oxygen, conductivity, temperature, or sampler data. The interval for storing
Teledyne Ism Flowlink Software / Engineering Specifications
Page 2 of 11
Released: February 24, 2008
3uawdinb3 6uuonuoW molj LZO- LL 911 : OEDL) LZO- LL 911 jol lerriwgns cost au6paial: ruawgoeny
60
am
a
data in each partition other than sampler partitions shall be selectable from 1, 2, 5, 10, 15,
30, 60, or 120 minutes, and the time span for each partition shall be entered in days and a
hours. Partitions for 6700 Series samplers, shall include an entry field for number of
samples. Each partition shall operate in either rollover, slate, or triggered slate mode. The
size, data storage interval, and data storage mode of each memory partition can vary. The
reading type, reading interval, time span, and recording mode for each partition shall be
visible even when the computer is not connected to the site.
b. In rollover mode, readings shall be stored in memory continuously. When the memory is -
full, the oldest reading shall be replaced by the newest reading.
c. In slate mode, readings shall be stored until the memory is full, at which time storage
shall stop. The memory shall hold these readings until it is restarted.
d. In triggered slate mode, the memory shall operate as a rollover partition until a triggering
event occurs. Once the triggering event occurs, the memory shall operate as a slate only
partition and store readings until it is full. The memory shall hold these readings until it is
restarted. The triggering event shall be an AND /OR combination of up to four conditions,
where each condition shall be either level, velocity, flow rate, volume, rainfall, pH,
dissolved oxygen, conductivity, temperature, or time. Each condition other than time
shall be either greater than or equal to a set point, less than or equal to a set point, or a
rate of change over a time period. A duration operator shall be available to modify the
condition. A time condition shall include up to four start and stop time periods, where
each time period shall be either daily, weekly, Monday through Friday, or a specific time.
A NOT operator shall be used to modify any condition other than time. Parentheses shall
be used to group conditions.
e. The software shall set up the memory partition in a 675 Logging Rain Gauge to store
rainfall data in rollover mode at an interval of 1, 2, 5, 10, 15, 30, 60, or 120 minutes.
f. Stored data retrieved from 4100 Series Flow Loggers, 4200 Series Flow Meters, 6700
Series Samplers with 700 Series Modules, 675 and 676 Logging Rain Gauges, and 581
Rapid Transfer Devices, shall be stored in an industry standard Microsoft Access
database.
6. Flow Conversion
a. The software shall set the primary device for the measurement site. Flow conversions
shall include weirs, flumes, the Manning formula, equations, area velocity, and data
points. Weirs shall include V- notch, rectangular with and without end contractions,
Cipolletti and Isco Flow Metering Inserts. Flumes shall include Parshall, Palmer -Bowlus,
Leopold- Lagco, HS, H, HL, and trapezoidal. The Manning formula shall include round,
U- shaped, rectangular, and trapezoidal channels with the slope and roughness coefficient.
Equations shall be a two term polynomial equation. Area velocity shall include round, U-
shaped, rectangular, and trapezoidal channels. Data points shall include up to 50 pairs of
points to convert level to flow rate or area. The software shall store four sets of data
points for 4100 Series Flow Loggers and 4200 Series Flow Meters.
b. The software shall retrieve the primary device from 4100 Series Flow Loggers, 4200
Series Flow Meters, and 6700 Series Samplers with 700 Series Flow Modules for use in
converting level and velocity data into flow rate.
c. Flow conversion attributes shall include an entry field for maximum level.
7. Sampler Control
Teledyne Isco Flowlink Software / Engineering Specifications
Page 3 of H
Released: February 14, 2008
luawd! nb3 6uuol! uoW Mold LZPLL 911 : a£ 4L) LZogl, 811 jol lell! wgns oosl auGpala1 : luawgoeSV
avm ao'
a
a. The software shall program the flow meter to enable a connected sampler. The flow
a
meter shall enable the sampler continuously, disable it continuously, or enable it
conditionally. The conditions for enabling a sampler with a 4100 Series Flow Logger or
4200 Series Flow Meter shall be selectable from the same types of conditions that are
used to trigger a triggered slate memory partition.
b. The software shall program the method by which the flow meter shall pace a connected
sampler. A 4100 Series Flow Logger or 4200 Series Flow Meter shall either flow pace or
trigger pace a sampler.
c. For flow pacing, the software shall program the volumetric interval at which the flow
meter shall send a signal to a connected sampler.
d. For trigger pacing, the software shall program a triggering condition and two time pacing
intervals, one that is used if the triggering condition is true and one that is used if the
triggering condition is false. The conditions for trigger pacing shall be selectable from the
same types of conditions that are used to trigger a triggered slate memory partition.
e. Units —The software shall set the units of measure for level, velocity, flow rate, total
flow, rainfall, dissolved oxygen, conductivity, and temperature.
f Alarms —The software shall set the alarm dialout conditions for a 4100 Series Flow
Logger or 4200 Series Flow Meter4. The software shall accept up to 5 telephone
numbers, plus a delay between calls and an enable for call back for acknowledgment. The
alarm dialout condition shall be selectable from the same types of conditions that are used
to trigger a triggered slate memory partition.
B.B. 21002100 SERIESSERIES FLOWFLOW MODULESMODULES
I.I. SiteSite InformationInformation
UponUpon connection connection toto aa site,site, thethe softwaresoftware shallshall displaydisplay andand allowallow editingediting ofof thethe instrument'instrument' ss
storedstored sitesite name,name, datedate andand time,time, andand GPSGPS information.information.
2.2. DevicesDevices
a.a. TheThe softwaresoftware shallshall displaydisplay thethe modulemodule type,type, modelmodel number,number, softwaresoftware revision,revision, andand
hardwarehardware revision revision ofof eacheach connected connected module.module. TheThe softwaresoftware shallshall allowallow thethe useruser toto changechange
thethe modulemodule name,name, andand illuminate illuminate thethe LEDLED onon eacheach module,module, soso thatthat thethe particular particular modulemodule
cancan bebe identified.identified.
b.b. TheThe softwaresoftware shallshall displaydisplay thethe connection connection settingssettings usedused toto communicate communicate withwith thethe site.site.
WhenWhen notnot connected,connected, thesethese settingssettings cancan bebe adjusted.adjusted.
3.3. Measurements Measurements
a.a. UponUpon connectionconnection toto aa site,site, thethe softwaresoftware shallshall displaydisplay inin aa singlesingle windowwindow thethe