TCLP Testing or subsequent testing required by
RCRA, shall be transported to an approved recycling facility or
hazardous waste landfill.
b) The hauler shall obtain the necessary insurance and the necessary
permits for transportation and shall provide evidence of such to
the additional insureds listed elsewhere in this Specification.
c) The transporter shall submit copies of his/her "Spill Contingency
Plan" to the Engineer and Owner prior to transporting any
Repair & Paint 009870 - 6
Countryview & Bluewater Tanks (2014) Job No. 41-459
material from the site. The "Spill Contingency Plan" shall detail
how spills or leaks which occur during transport shall be dealt
with.
d) The hauler shall have or shall obtain an identification number
from the USEPA, the Florida Department of Environmental
Protection (FDEP) and all other applicable state and local
licenses and permits.
e) All containers and the labeling of the containers shall adhere to
the U.S. Department of Transportation's regulations (49 CFR
Part 172) and the HMTA.
G. Disposal of Material:
1. All material classified as hazardous, as determined by the aforementioned TCLP
testing or subsequent testing required by RCRA, shall be transported to:
a. An approved recycling facility, or
b. An approved treatment facility to reduce the leachable concentration levels to
below the allowable regulatory limits and disposed in a local and/or state
approved waste landfill.
2. All transporting, recycling, treatment, and disposal shall be in strict accordance
with federal and state laws including but not limited to RCRA, TSCA, HMTA,
the USEPA and the FDEP regulations.
a. The name of the recycling, treatment and/or disposal facility shall be
submitted to the Engineer and Owner for approval prior to removing any
material from the project site.
b. The disposal or recycling facility shall have or shall obtain an identification
number from the USEPA, the Florida Department of Environmental
Protection (FDEP) and all other applicable state and local licenses and
permits.
c. The Contractor shall be responsible for obtaining the proper signatures of the
hauler and designated receiving facility on the "manifest" form.
d. Payment will not be released for this item until this documentation has been
received by the Owner.
3. Payment :
a. All costs associated with the transporting, recycling of the material or
treatment, and disposal of the material in an approved hazardous waste
facility shall be paid for by the Owner. The Contractor shall still keep the
exterior and interior removed paint debris separate from each other and shall
store the debris in separate leak-proof covered containers.
b. Within 20 days of the Owner contacting the Contractor, the Owner shall
furnish and deliver to the site containers for transporting the hazardous
material.
Repair & Paint 009870 - 7
Countryview & Bluewater Tanks (2014) Job No. 41-459
4. The Contractor shall then fill the containers with the hazardous material.
5. The Owner shall then be responsible for the transporting and recycling of the
material or treatment and/or disposal of the material in an approved hazardous
waste facility.
1.9 HOURS OF OPERATION
No repairing, cleaning or painting is to be done in the night period between sunset and
sunrise. Further, blasting operations or any other operation that requires power equipment
shall be limited to 8 AM - 6 PM (local time) on Saturday and 9 AM - 6 PM (local time) on
Sunday. The times for Work shall also comply with local, state, and federal regulations
and laws regarding working hours, overtime, etc. County ordinances shall be adhered to
regarding noise and interference to surrounding property owners. If temperatures and
weather conditions warrant nighttime work, a written request to the OWNER and
ENGINEER shall be approved prior to any work being initiated.
1.10 EMERGENCY INFORMATION
A. The CONTRACTOR shall post information concerning emergency medical, fire,
rescue and hazardous waste phone numbers from which personnel on the site can
obtain information if needed.
B. The emergency information shall be posted a central position, located so it is visible
and accessible twenty-four (24) hours a day for the entire length of time that the
CONTRACTOR is performing Work at the tank site.
PART 2 - PRODUCTS
2.1 BLAST ABRASIVE
A. General
1. All of the abrasives shall be steel grit (size 50-80).
2. The abrasive shall be properly stored, and it shall be free from contaminant,
including but not limited to paint, dirt, moisture, oil, or chlorides, which can cause
premature failure of the coating.
3. Use of abrasive on the exterior of the tank shall be based not only on its
compliance with the technical application of the coatings, but also on its lack of
nuisance to surrounding property.
4. The CONTRACTOR shall submit manufacturer's published product data sheets
Repair & Paint 009870 - 8
Countryview & Bluewater Tanks (2014) Job No. 41-459
for the type of abrasive, grade, and the resulting profile of the abrasive to be used
to the ENGINEER for approval prior to the start of any cleaning operations.
2.2 COATINGS
A. All coatings for the job shall be obtained from a single approved coatings
manufacturer. Products proposed for use, other than those specified, must be
submitted in writing at least 10 days before the bid date. Proposal shall include
product data sheets, MSDS sheets, performance criteria as listed in Section 3.12 of
these specifications as well as a list of a minimum of 15 tanks (including location,
Engineer’s name and phone number, Owner name and phone number) which have
utilized the proposed coating system. References shall have rendered satisfactory
service for at least 5 years. It is incumbent upon the proposer to prove that the
materials submitted meet the generic type as well as the performance requirements
established in these specifications.
B. Coatings shall be manufactured by the following approved manufacturer:
Tnemec Company Incorporated
C. Thinners shall be as recommended by the approved coating manufacturer.
D. All materials shall be furnished new and delivered to the project site in the original
factory sealed containers which are clearly and properly labeled by the coating
manufacturer showing the manufacturer’s name, product number, type of coating,
batch number and expiration date.
E. The materials shall be stored, handled and used in accordance with all manufacturers’
published product data, including all requirements listed on the Material Safety Data
Sheets (MSDS).
F. Coating Systems
1. Except as modified herein, all coating systems shall comply with the following:
a. AWWA D102-06 Outside Coating System No. 4 (OCS-4-modified): Generic
Description - A four-coat system comprised of a zinc-rich primer, one
polyamidoamine epoxy and one aliphatic urethane intermediate coat, and a
fluoro-urethane finish coat. All replacement parts (ladders, hatches, etc.) shall
have a five-coat system with the addition of a shop-applied zinc-rich primer to
the above described system.
b. AWWA D102-11 Inside Coating System No. 3 (ICS-3, Modified): Generic
Description - A two coat system consisting of an organic zinc-rich primer,
with a 100% solids, fast setting, epoxy lining. Replacement ladder shall have
Repair & Paint 009870 - 9
Countryview & Bluewater Tanks (2014) Job No. 41-459
a three coat system with the addition of a shop-applied zinc-rich primer to the
above described system.
c. All coatings and coating systems in contact with potable water shall comply
with ANSI/NSF, International Standard 61.
d. Table 1 in the Appendix has been included to summarize the coatings. This
quick reference is included for the contractor’s convenience, but is not
intended to supersede the technical specifications.
2.3 ELASTOMERIC SEALANT
A. Elastomeric Sealant shall be an NSF approved, one part polyurethane sealant. Product
shall be SIKAFLEX-1 as manufactured by SIKA Corporation.
2.4 SEAM SEALER & SURFACER
A. Seam sealer and surfacer shall be an NSF 61 approved solventless epoxy seam sealer
and shall be Tnemec 215 Surfacer. The seam sealer and surfacer shall be
recommended by the manufacturer of the interior paint system.
2.5 DEGREASING AGENT
A. A degreasing agent such as Great Lakes Extra Muscle Pre-Paint Cleaner or approved
equal shall be used for the pre-inspection washouts as required, if applicable to project.
2.6 MATERIAL SAFETY DATA SHEETS (MSDS)
A. An MSDS shall be posted at the job site for each chemical product on the job site
including, but not limited to, coatings, thinners, solvents, disinfecting agents, abrasives,
welding materials, and flexible sealant material.
B. An MSDS for each chemical product on the job site shall also be submitted to the
ENGINEER prior to starting any work.
PART 3 - REPAIRING AND REPAINTING THE TANK
3.1 PRELIMINARIES
A. The CONTRACTOR shall notify the OWNER and the ENGINEER at least seven (7)
days before starting the Work at the site. The CONTRACTOR shall reconfirm the
commencement of Work with the OWNER and ENGINEER twenty-four (24) hours
prior to starting Work at the site.
B. The tank shall be drained during all cleaning, painting and curing of the coatings.
Repair & Paint 009870 - 10
Countryview & Bluewater Tanks (2014) Job No. 41-459
C. All operations which would include closing valves,