previously, the City places a great deal of emphasis on public education and public
outreach programs to infonn citizens of various water conservation measures and water reduction
the City by
programs. These programs, while expensive to implement, provide an indirect benefit to
promoting wise and efficient use of the community water supply. However, the total volume of inefficient
use of the water
system through the implementation of these programs is difficult to quantify.
REGIONAL WATER SUPPLY PLAN 35 CITY OF FORT WALTON BEACH
As part of the City's Public Education campaign, the Utilities Department began offering Water
Saver Kits to citizens upon request several years ago. These kits contain several devices to conserve water in
the home including toilet tank displacement bags, leak detection tablets, replacement showerheads, water
faucet aerators, and conservation tips. Collectively when installe~ these devices can reduce household water
consumption by 100 gallons, or more, per day. Customers that call regarding abnonnally high water bills or
those wishing to reduce their nonnal monthly consumption are offered these kits as an incentive to reduce
their monthly expense for water use. Though public education is very important, its impact is not included
in the preparation of future water production needs.
6. 7 PLUMBING CODE REVISIONS
In 1992, the federal government established National Water Efficiency Requirements for plumbing
products with the passage of the Federal Energy Policy Act. Almost every toilet, urinal, shower head and
faucet manufactured after January 1, 1994 must meet Uniform National Conservation Standards. The
Southern Standard Plumbing Code allowed two years for supply houses to clear inventories of old style
fixtures. As of January 1, 1996 all new or renovated buildings must install fixtures meeting the new
standards.
Residential water savings from retrofitting conventional toilets, showerheads, and faucets range from
13. 5 gpcd for replacement of fixtures installed after 1980 to 33. 5 gpcd for pre- 1980 fixtures. Reductions in
water demand from more efficient plumbing fixture usage over the next 25 to 40 years will be continuing
and incremental as existing high-volume equipment is replaced with new, more efficient models. Per capita
residential use from faucets, showerheads, and commodes is projecte~ on a national
average, to drop from
45 gpcd in 1995 to 21 gpcd by 2026 (Vickers, 1993).
As of January 1, 1996, all new or renovated buildings must install plumbing fixtures that meet the
new standards. These new efficient
plumbing devices will certainly lessen the impact of new construction on
potable water demands, however, given the fact that the City expects very limited new construction in the
next ten years, any reductions in future water
production needs would be minimal.
SECTION 7 - WATER SUPPLY NEEDS
The City of Fort Walton Beach maintains records of raw water withdrawals and metered
consumption on a monthly basis each year. The following table indicates the raw water withdrawals and
metered consumption from 2000 to 2007.
T abIe .IX U.lstone alW ater Pro duetton andC onsumptton D ata
Raw Water Withdrawals Treated Water Production
Average Maximum Maximum Average Maximum Maximum
YEAR Day Day Month Year Total Day Day Month Year Total
2000 3,222,000 4,495,000 114, 093, 000 1, 175,993, 000 3, 199, 000 4,375,000 114, 114,000 1, 167, 732,000
2001 3, 011, 000 4,010,000 110, 896,000 1, 098,890,000 2,975, 000 3, 992,000 110, 175,000 1, 085, 702,000
2002 2, 937, 000 4,323,000 106, 649, 000 1, 071, 824,000 2, 917,000 3, 824,000 104, 861, 000 1, 064,808,000
2003 2, 804,000 4,221, 000 98, 134,000 1, 023, 603, 000 2, 809, 000 3, 652,000 97, 881, 000 1, 025,279, 000
2004 2, 913,000 4, 686, 000 97, 714, 000 1, 066,285, 000 2, 877,000 3, 893, 000 97,837, 000 1, 052,809, 000
2005 2, 980,000 4,375, 000 103, 891, 000 1, 087,722,000 2,883, 000 3,782,000 99, 845, 000 1, 052,446, 000
2006 3, 110,000 4,791, 000 116, 023, 000 1, 135,091, 000 3, 098,000 4,345,000 115,445, 000 1, 130, 743,000
2007 2, 897, 000 3, 902, 000 103, 246,000 1, 057,231, 000 2, 871, 000 3,860,000 102, 712,000 1, 047, 956, 000
Aver~ e 2, 984,250 4, 350,375 106,330, 750 1, 089,579, 875 2, 953, 625 3, 965,375 105, 358,750 1,078,434,375
REGIONAL WATER SUPPLY PLAN 36 CTIY OF FORT WALTON BEACH
As previously note~ the Individual Water Use Pennit limits were not exceeded during the period
between 2000 and 2007. Using the historical treated water production figures from Table IX and the
estimated BEBR populations, the average per capita water demands can be calculated.
T abIe .X H.lStonc alOverallP er C aplta
. Water D eman d
ADR Treated Average Per MDR Treated Maximum Per
Service
Year Water Capita Water Capita
Population Production Demand Production Demand
2000 20,640 3, 199, 000 154.99 4,375,000 211.97
2001 20,822 2, 975, 000 142. 88 3, 992,000 191.72
2002 20, 926 2, 917, 000 139.40 3, 824,000 182.74
2003 21, 200 2, 809, 000 132.50 3, 652,000 172.26
2004 21, 307 2, 877,000 135.03 3, 893, 000 182.71
2005 21, 421 2, 883,000 134.59 3,782,000 176. 56
2006 21, 493 3, 098, 000 144.14 4,345, 000 202. 16
2007 21, 699 2, 871, 000 132.31 3, 860,000 177. 89
Average 2, 953, 625 139.48 3, 965,375 187.25
The City of Fort Walton Beach utilizes an overall average water demand level of service standard of
150 gallons per capita per day in its Comprehensive Plan to estimate the future demands based on
population density build-out throughout the City. As noted in Table X,the actual average level of service
provided by the City' s water system is less than the standard level of service, allowing a " safety factor" for
future planning.
7. 1 FUTURE WATER NEEDS PROJECTIONS
Based on the projected annual growth rate of 0.70 percent per year and the withdrawal rates and
production from 2007, the future raw water withdrawal and treated water production needs were projected
from 2008 through 2017 ( See Table XI).
1thdrawal & T reate dWater Pod
T able .XI Future Raw W ater w. r ucUon Pr01ecuon
. s
Future Raw Water Withdrawals Future Treated Water Production
Average Maximum Maximum Average Maximum Maximum
YEAR Day Day Month Day Day Month
2008 2, 917, 000 3, 929,000 103, 969,000 2, 891, 000 3, 887,000 103,431, 000
2009 2, 938, 000 3, 957,000 104, 697, 000 2, 911, 000 3, 914,000 104, 155,000
2010 2, 958,000 3, 985, 000 105,429, 000 2,932,000 3, 942,000 104,884,000
2011 2,979,000 4,012,000 106, 167, 000 2,952,000 3, 969,000 105, 618,000
2012 3,000,000 4,040,000 106,911, 000 2,973, 000 3, 997,000 106,358,000
2013 3,021, 000 4,069,000 107, 659, 000 2, 994,000 4,025,000 107, 102,000
2014 3,042,000 4,097, 000 108,413, 000 3, 015,000 4,053, 000 107, 852,000
2015 3, 063, 000 4, 126, 000 109, 171, 000 3, 036,000 4,082,000 108,607, 000
2016 3, 085,000 4, 155, 000 109, 936, 000 3, 057,000 4, 110,000 109,367, 000
2017 3, 106,000 4, 184,000 110, 705,000 3, 078,000 4, 139,000 110, 133,000
REGIONAL WA1ER SUPPLY PLAN 37 CITY OF FORT WALTON BEACH
Through the year 2017, the City' s water system has the capacity to provide sufficient potable water
from the Roridan aquifer. At this time, there is no need to increase current production levels at any of the
existing water wells. In the latest CUP renewal application, the City did request an increase in the Maximum
Monthly Rate of Withdrawal (MMR) from 120 million gallons per month to 125 million gallons per month
based on the 2006 withdrawal rates. The 2006 withdrawal rates were much higher than average due to the
drought conditions the area experienced. In 2007, the withdrawal rates returned to below average
conditions.
The average daily demand for the ten year projection was detennined by utilizing the withdrawal
rates from 2007 and adjusting the rates by the 0.70 percent annual growth rate each year to 2017. The
average daily demand in 2007 was 2, 897,000 gallons per day, and the average daily demand projected for
2017 is 3, 106, 000 gallons per day. A surplus of 494,000 gallons per day will exist in the City' s CUP
withdrawal limit. The surplus would be capable of serving an additional 3,290 persons using the standard
level of service of 150 gallons per capita per day.
SECTION 8 - WATER STORAGE AND DISTRIBUTION SYSTEM NEEDS
The ability of the City' s existing system to meet both current and future water supply needs can be
assessed by reviewing the current and future demands versus the supply capacity of the City's nine wells.
The limitation of the City' s existing system is not the wells or the equipment, it is the withdrawal rate limits
imposed by the NWFWMD as part of the Consumptive Use Permit.
The City's existing system is capable of providing over 9. 2 million gallons of potable water per day.
However, the CUP limits the system to 3. 60 million gallons per day on an