starting construction,
completing construction, or attaining final compliance;
f. Failure to provide within forty-five (45) days after the due date, any required reports, including baseline
monitoring reports, reports on compliance with categorical Pretreatment Standard deadlines, periodic self-
monitoring reports, and reports on compliance with compliance schedules;
g. Failure to accurately report non-compliance; or
h. Any other violation(s), which may include a violation of Best Management Practices, which Director
determines will adversely affect the operation or implementation of the local pretreatment program.
(7) In the event of violation of this article, the County Health Department or Board's authorized employee may
verbally instruct the Owner as to the necessary corrective action. If the owner fails to carry out verbal
instructions in a timely manner or if a serious violation or hazard to public health exists, the Health Officer or
Board's authorized employee, may issue to the Owner a written order stating the nature of the violation, the
corrective action and the time limit for completing the corrective action. This time limit will be not less than 24
hours or more than six months depending upon the type and severity of the violation. The offender shall within
the period of time stated in such notice, permanently cease all violations. The record of the mailing of said
notice or order shall be prima facie evidence thereof and failure of said owner or owners to receive same shall
in no way affect the validity of any proceedings conducted pursuant to this article.
(8) Any user who is found to have violated an order of the Health Officer or Board's authorized employee or
who willfully or negligently fails to comply with any provision of this article, and the orders, rules, regulations
and permits issued hereunder, shall be punished in accordance with Florida Statutes. Each day on which a
violation shall occur or continue, shall be deemed a separate and distinct offense. In addition to the penalties
provided herein, the Board may recover reasonable attorney's fees, court costs, court reporters' fees and other
expenses of litigation by appropriate suit at law against the person found to have violated this article or the
orders, rules, regulations and permits issued hereunder.
(9) Any person who knowingly makes any false statements, representation or certification in any application,
record, plan or other document filed or required to be maintained pursuant to this article, or who falsifies,
tampers with, or knowingly renders inaccurate any meter or monitoring device or measurement method
required under this article, shall, upon conviction, be punished in accordance with Florida Statutes.
(10) A person violating any provision of this article authorizing the aforementioned action by the Health
Officer or Board's authorized employee shall be charged the normal and usual charges for discontinuance and
disconnection of said water and sewer services and the usual charges for re-commencing said water and
sewer services as specified in Appendix A.
Secs. 24-325. - 24-340. - Reserved.
Page 69 of 118
DIVISION 11. - CROSS CONNECTION CONTROL STANDARDS
Sec. 24-341. - Generally.
Sec. 24-342. - Statutory authority.
Sec. 24-343. - Applicability.
Sec. 24-344. - Definitions.
Sec. 24-345. - Responsibilities of department, customers.
Sec. 24-346. - Backflow prevention devices required.
Sec. 24-347. - Inspections.
Sec. 24-348. - Records.
Sec. 24-349. - Maintenance; testing.
Sec. 24-341. - Generally.
The County Water and Sewer Department, in its operation of a public potable water supply system, is required to
ensure protection of the public health through the provision of minimum requirements and standards for design,
construction, operation and maintenance of its system. It is essential that physical cross connections, which
create or have the potential to create an imminent and substantial danger to public health, be eliminated from the
distribution system and plumbing systems of customers. Backflow can result in the potable water system
becoming a transmitter of disease, toxic materials and other hazardous liquids. Therefore, it is necessary to
establish and maintain a cross connection control to protect the health of water customers by the control of actual
and/or potential cross connections through methods of containment and/or isolation. In addition to Division 11, all
current and future state and federal ordinances, statues, and codes apply and are enforceable.
Sec. 24-342. - Statutory authority.
This division is enacted pursuant to the following:
(1) Florida Safe Drinking Water Act, Sections 403.850 through 430.864, Florida Statutes.
(2) Florida Administrative Code, Chapter 62-22.107, part 4, subpart b: "Community water supply systems
are required to establish a routine cross connection control program for the purpose of detecting and
preventing cross connections that create or have the potential to create an imminent and substantial danger
to public health by and from contamination due to the cross connection. Upon detection of a prohibited cross
connection both community and non-community water systems shall either eliminate the cross connection
by installation of an appropriate backflow prevention device acceptable to the department (F.D.E.P.) or
discontinue service until the contaminant source is eliminated. Such program shall be developed utilizing
accepted practices of the American Water Works Association guidelines as set forth in AWWA manuals
M14, Backflow Prevention and Cross Connection Control, and Cross Connections and Backflow Prevention,
2nd Edition."
Sec. 24-343. - Applicability.
All territory within Okaloosa County served by the county water and sewer system shall be embraced by the
provisions of this division.
Sec. 24-344. - Definitions.
The following words, terms and phrases, when used in this division, shall have the meanings ascribed to them in
this section, except where the context clearly indicates a different meaning.
Page 70 of 118
Atmospheric vacuum breaker means a backflow prevention device which is operated by atmospheric pressure in
combination with the force of gravity. The unit is designed to work in a vertical plane only. The moving part
consists of a poppet valve, which must be carefully sized to slide in a guided chamber and effectively shut off the
reverse flow of water when a negative pressure exists.
Auxiliary water supply means any water supply on or available to the premises other than the purveyor's approved
public potable water supply. These auxiliary water supplies may include water from another purveyor's public
potable water supply or any natural source(s) such as a well, spring, river, harbor, etc., or "used waters" or
industrial fluids." These waters may be polluted, contaminated, or may be objectionable and constitute an
unacceptable water source over which the water purveyor does not have sanitary control.
Back pressure means the reversal of normal flow in a system due to an increase in the downstream pressure
which is greater than the supply pressure. Back pressure is created whenever the downstream pressure exceeds
the supply pressure. This is possible in installations such as heating systems, elevated tanks, pumps which
malfunction by pumping backward, etc. An example would be an open valve on a supply line to a boiler operating
at 100 pounds of pressure at the same time that the pressure in the county water main was below such pressure.
As water tends to flow in the direction of least resistance, a back pressure condition would be created and the
contaminated boiler water would flow into the potable water supply.
Back siphonage means the reversal of normal flow in a system caused by a negative pressure (vacuum or partial
vacuum) in the supply piping. Back siphonage can be created when there is a reduction of pressure in the water
supply due to nearby firefighting, repairs or breaks in the county water main, etc. The effect is similar to sipping
soda by inhaling through a straw, which induces a flow in the opposite direction.
Backflow means the reversal of the normal direction of flow in water service lines. This reversal of flow can result
in contamination of the public potable water supply if there is an unprotected cross connection in a customer's
internal plumbing system. There are two causes of backflow; back pressure and back siphonage.
Backflow prevention device means a device to counteract back pressure or prevent back siphonage.
Backflow prevention device approved means the term approved backflow prevention device shall mean a device
that has met the requirements of one or more of the following standards:
(a) AWWA C-506 Standard for backflow prevention devices, reduced
pressure principle and double check valve types
(b) ASSE 1001 Atmospheric type vacuum breakers
(c) ASSE 1011 Hose connection vacuum breakers
(d) ASSE 1020 Pressure type vacuum breakers
(e) ASSE 1024 Dual check type backflow preventer. (Residential Use
Only)
(f) ASSE 1013 Reduced pressure principle back pressure backflow
preventers
(g) ASSE 1015 Double check valve type back pressure backflow
preventers
(h) USC FCC University of Southern California Foundation for cross-
connection control and hydraulic research
Containment means protection of the public potable water supply by installation of an approved backflow
prevention device in the customer's water service line which would prevent the reversal of flow from the service
line into the public water supply.
Contaminant means any foreign substance that degrades the quality of the public potable water supply or may
create a health hazard.
Page 71 of 118
Cross connection means a direct arrangement of a piping line which allows the potable water supply to be
connected to a line which actually contains, or might potentially contain, a contaminant or pollutant. Any physical
arrangement whereby a public water supply system is connected, directly, or indirectly, with any other water
supply system, sewer, drain, conduit, pool, storage reservoir, plumbing fixture or other device or facility which
contains or may contain contaminated or polluted water, industrial fluids, sewage or other waste or liquid of
unknown or unsafe quality, which may be capable of imparting contamination or pollution to the public water
supply system as a result of backflow. An example would be a common garden hose attached to a hose bib with
the end of the hose lying in a sink used for mixing pesticides. Other examples include, but are not limited to;
bypass arrangements, jumper connections, removable sections, swivel or change-over devices, or any other
temporary or permanent devices or facilities through which or because of which backflow could occur.
Double check valve assembly means an assembly composed of two single, independently acting check valves,
including tightly closing shutoff valves located at each end of the assembly and suitable connections for testing
the water tightness of each check valve.
Fire line means any dedicated line which feeds a fire protection sprinkler system.
Health hazard means any condition, devices, or practices in any water supply system, or in its operations, which
create or may create a danger to the health and well-being of the water customer.
Industrial fluids means any fluids or solution that may be chemically, biologically or otherwise contaminated or